Automatic fire foam gun-ZDMS0.8/30P-TY |
Product details:
The automatic fire fighting gun is composed of fire fighting gun body, signal processor and field manual control panel. It combines micro-control technology, infrared/ultraviolet sensing and detection technology, mechanical rotation control technology, image transmission technology, automatically looking for the precise location of the ignition point and effectively and quickly extinguish the fire source; According to the line of ignition system is automatic 逬 dc on or spray water injection of fancy, effective fire at the same time, and can protect to the personal and property safety; Has the field manual operation control and the image display function; According to the linkage signal of other fire alarm system, the fire source can be started compulsively; The infrared/ultraviolet dual-band detection technology can effectively detect the fire source and improve the ability of anti-environmental interference. And ground sensitivity parameter setting and debugging.
Product parameters:
Model |
ZDMS0.8/20S |
|
ZDMS0.80/40S-TY |
ZDMS0.8/30P-TY泡沫 |
Fixed working pressure |
0.8MPa |
0.8MPa |
0.8MPa |
0.8MPa |
Working pressure upper limit |
1.6MPa |
1.6MPa |
1.6MPa |
1.6MPa |
Rated flow |
20L/S |
30L/S |
40L/S |
30L/S |
Protection radius |
50m |
55m |
60m |
45m |
Overlooking return angle |
-90°~60°(adjustable) |
-90°~60°(adjustable) |
-90°~60°(adjustable) |
-90°~60°(adjustable) |
Targeting time |
60s |
60s |
60s |
60s |
Power line voltage |
24VDC |
24VDC |
24VDC |
24VDC |
Biggest actuation power |
130W |
130W |
130W |
130W |
Installation height |
8?30 |
8?30 |
8?30 |
8?30 |
Monitoring radius |
80m |
80m |
80m |
80m |
Jet medium |
water |
water |
water |
foam/water |
Performance feature:
=Large flow, long range, and faster to extinguish early fires
=The rotating mechanism has clutch function to protect the motor effectively
=With electrically operated column/fog nozzles
=Dual-band detection can effectively improve anti-jamming capability
=It has field manual control function
=It has the function of image transmission
=With other fire alarm system linkage function
=Field ground sensitivity parameter setting, convenient for debugging